Leave Your Message

Industrial Water Cooled Chiller - High Efficiency Cooling Solutions from China Suppliers and Factory

An industrial water-cooled chiller is a powerful refrigeration system tailored for continuous and precise cooling in challenging environments. Designed to offer reliable temperature control for industrial equipment and manufacturing processes, these chillers are notable for their robust construction and high-efficiency components. Many China suppliers provide custom configurations to meet specific operational needs, making them perfect for various factory applications. For businesses seeking dependable cooling solutions, investing in an industrial water-cooled chiller from renowned manufacturers can enhance operational efficiency and performance

    Product Feature
    • Adopt compressor imported from Europe and America
    • The copper pipe adopts oxygen free welding method
    • RS485 communication function to realize automatic management (optional)
    • Imported advanced components with long service life
    • Siemens SCHNEIDER · LG · MOELLER · West is adopted for electrical appliances
    • Control mode: imported microcomputer or PLC control (optional)
    • Perfect safety protection, fault display, repair and maintenance without professional personnel
    • High efficiency evaporator and condenser can save energy by more than 30%

    Main Types

    Industrial water-cooled chillers are primarily categorized based on their outlet water temperature and specific applications:

    🌡️ 1. Standard Temperature Type

    Outlet Temperature: Typically > 5°C

    Applications: Cooling for injection molding machines, extruders, die-casting machines, laser equipment, welding machines, and as primary cooling for central air-conditioning systems.

    ❄️ 2. Low-Temperature Type

    Outlet Temperature: Typically ranging from -20°C to +5°C

    Features: Employs two-stage compression or cascade refrigeration cycles, utilizing low-temperature refrigerants.

    Applications: Pharmaceutical reaction kettles, chemical crystallization, food quick-freezing, low-temperature laboratories, and vacuum coating.

    🔒 3. Explosion-Proof Type

    Features: All electrical components (motors, switches, controllers) are designed to be explosion-proof, preventing electrical sparks from igniting hazardous atmospheres.

    Applications: Petrochemical plants, coal mines, and painting workshops.

    🛡️ 4. Corrosion-Resistant Type

    Features: Casing, heat exchangers, piping, etc., constructed from stainless steel or special anti-corrosion materials with specific surface treatments.

    Applications: Electroplating shops, chemical plants, offshore platforms, and high salinity or humidity environments.


    Key Components & Industrial-Grade Features

    Beyond standard compressors, condensers, evaporators, and expansion devices, industrial chillers place special emphasis on:

    ⚙️ 1. Compressor

    Types: Heavy use of screw compressors (stable, durable, wide modulation range) and centrifugal compressors (for very large capacities). Some large low-temperature units employ cascade systems.

    Redundancy: Multiple compressor parallel design is common, ensuring continued operation if one fails.

    🔁 2. Heat Exchangers (Evaporator/Condenser)

    Design: Often feature oversized shell-and-tube heat exchangers with larger fouling factor allowances.

    Materials: May use stainless steel tubes or titanium tubes (for seawater or highly corrosive cooling water).

    💻 3. Control System

    Intelligence: Advanced PLCs with touchscreen HMIs, featuring remote monitoring, fault, data logging, and energy management.

    Integration: Capable of communicating with primary production line control systems (e.g., SCADA, DCS) for control and precise regulation.

    🛡️ 4. Protection Systems

    Includes not only standard high/low pressure and overcurrent protection, but also oil pressure differential protection, freeze protection, low-flow protection, phase protection, etc., ensuring safe operation under harsh conditions.


    Typical Industrial Applications
    🏭
    Plastics Industry Cooling for injection molding machine molds, directly impacting product quality and cycle time.
    🧪
    Chemical & Pharmaceutical Cooling exothermic reactions in process vessels, controlling reaction rates and safety.
    🔧
    Machining & Lasers Cooling for CNC machine spindles, laser sources, and welding equipment, ensuring precision and longevity.
    🍔
    Food & Beverage Cooling for mixing, fermentation, and packaging processes in production lines.
    💡
    Electronics Industry Cooling for semiconductor manufacturing, ultrasonic cleaning, and testing equipment.
    ⚡
    Energy & Metallurgy Transformer oil cooling, blast furnace auxiliary system cooling.
    16
    15
    14

    Schematic Diagram
    Schematic Diagram

    Specification
    Parameter   Model 03WS 05WS 06WS 08WS 10WD 12WS 15WD 20WD 25WS 30WF 40WF 50WD
    Refrigeration Capacity kW 7.7 14.2 8.98 18.95 28.4 33.5 37.9 58.2 67 75.8 116.4 135.6
    ×10⁴kcal/hr 0.66 1.22 1.45 1.63 2.44 2.88 3.26 5 5.76 6.52 10.01 11.66
    Consumed Power (kW) 2.49 3.81 4.29 5.29 7.62 8.78 10.98 15.34 17.95 21.96 30.28 35.50
    Running Amp (A) 4.73 7.79 7.76 10.9 15.58 17.1 22.6 32.38 33.26 45.2 64.06 65.82
    Compressor Number 1 1 1 1 2 1 2 2 1 4 4 2
    Power (kW) 1.94 3.26 3.74 4.74 6.52 7.68 9.48 13.14 15.75 18.96 26.28 31.5
    Current (A) 3.63 6.69 6.66 9.80 13.38 14.90 19.6 27.98 28.86 39.2 55.96 57.72
    Refrigerant Type R22 R410A R22 R410A
    Control Mode External Balance Type Thermal Expansion Valve
    Pump Type High-Efficiency Low-Noise Centrifugal Pump
    Power (kW) 0.55 0.55 0.55 0.55 1.1 1.1 1.5 2.2 2.2 3 4 4
    Current (A) 1.1 1.1 1.1 1.1 2.2 2.2 3 4.4 4.4 6 8.1 8.1
    Head (m) 22 21 21 20.5 25.5 24.5 23.5 27.5 27 33 29 29
    Condenser Water Pipe DN25 DN40 DN50 DN65
    Water Flow Rate (m³/h) 1.73 3.11 3.70 4.25 6.22 7.32 8.51 12.74 14.99 17.01 25.47 29.99
    Evaporator Water Pipe DN25 DN40   DN50 DN65
    Water Flow Rate (m³/h) 1.40 2.55 3.06 3.44 5.10 5.99 6.87 10.47 12.28 13.75 20.95 24.56
    Size Length (mm) 900 900 900 1300 1300 1450 1450 1800 1800 2200 2500 2500
    Width (mm) 650 650 650 800 800 900 900 1000 1000 1350 1350 1350
    Height (mm) 1090 1090 1090 1750 1750 1750 1750 1800 1800 1400 1800 1800
    Tank Volume (L) 50 75 90 120 120 160 160 250 300 300 500 500
    Total Weight (kg) 150 220 260 310 360 450 650 850 1050 1250 1350 1400

    Products Detail
    Industrial Water Cooled Chiller (1)
    Industrial Water Cooled Chiller (4)
    Industrial Water Cooled Chiller (2)
    Industrial Water Cooled Chiller (3)

    Frequently Asked Questions (FAQ)
    ❓ What is the difference between a standard temperature and a low-temperature industrial water-cooled chiller?
    A standard temperature chiller typically delivers outlet water above 5°C and is suitable for general industrial cooling such as injection molding or laser equipment. A low-temperature chiller operates between -20°C and +5°C using two-stage compression or cascade refrigeration, making it ideal for pharmaceutical reactions, chemical crystallization, and food quick-freezing applications.
    ❓ What type of compressor is used in industrial water-cooled chillers?
    Industrial water-cooled chillers primarily use screw compressors for their stability, durability, and wide modulation range. Centrifugal compressors are used for very large capacity requirements. Many units also feature multiple compressors in parallel to ensure continued operation in the event of a single compressor failure.
    ❓ Which refrigerants are used in these industrial chillers?
    The chillers use either R22 or R410A refrigerant depending on the model. For example, models 03WS through 20WD and 30WF–40WF use R22, while models 25WS and 50WD use R410A. All models use an External Balance Type Thermal Expansion Valve as the refrigerant control mode.
    ❓ Can the industrial water-cooled chiller be integrated with a production line control system?
    Yes. The control system features advanced PLCs with touchscreen HMIs and supports RS485 communication (optional). It can be integrated with SCADA and DCS systems, enabling remote monitoring, fault diagnosis, data logging, energy management, and precise regulation in coordination with the primary production line.
    ❓ What safety protection features are included in the industrial water-cooled chiller?
    The units are equipped with comprehensive protection systems including high/low pressure protection, overcurrent protection, oil pressure differential protection, freeze protection, low-flow protection, and phase protection. Fault display functions allow maintenance without the need for professional personnel, ensuring safe and reliable operation under demanding industrial conditions.
    ❓ Is there a corrosion-resistant version available for harsh chemical environments?
    Yes. The corrosion-resistant type features a unit casing, heat exchangers, and piping constructed from stainless steel or special anti-corrosion materials with specific surface treatments. This version is designed for use in electroplating shops, chemical plants, offshore platforms, and environments with high salinity or humidity.