Industrial Water Cooled Chiller - China Suppliers & Factory for Reliable Process Cooling Solutions
- Adopt compressor imported from Europe and America
- The copper pipe adopts oxygen free welding method
- RS485 communication function to realize automatic management (optional)
- Imported advanced components with long service life
- Siemens, SCHNEIDER, LG, MOELLER, West is adopted for electrical appliances
- Control mode: imported microcomputer or PLC control (optional)
- Perfect safety protection, fault display, repair and maintenance without professional personnel
- High efficiency evaporator and condenser can save energy by more than 30%
Industrial water-cooled chillers are primarily categorized based on their outlet water temperature and specific applications:
Outlet Temperature: Typically > 5°C
Applications: Cooling for injection molding machines, extruders, die-casting machines, laser equipment, welding machines, and as primary cooling for central air-conditioning systems.
Outlet Temperature: Typically ranging from -20°C to +5°C
Features: Employs two-stage compression or cascade refrigeration cycles, utilizing low-temperature refrigerants.
Applications: Cooling for pharmaceutical reaction kettles, chemical crystallization, food quick-freezing, low-temperature laboratories, and vacuum coating.
Features: All electrical components (motors, switches, controllers) are designed to be explosion-proof, preventing electrical sparks from igniting hazardous atmospheres.
Applications: Petrochemical plants, coal mines, and painting workshops.
Features: Casing, heat exchangers, piping, etc., are constructed from stainless steel or special anti-corrosion materials with specific surface treatments.
Applications: Electroplating shops, chemical plants, offshore platforms, and high salinity or humidity environments.
Beyond standard compressors, condensers, evaporators, and expansion devices, industrial chillers place special emphasis on:
- Types: Heavy use of screw compressors (stable, durable, wide modulation range) and centrifugal compressors (for very large capacities). Some large low-temperature units employ cascade systems.
- Redundancy: Multiple compressor parallel design is common, ensuring continued operation if one fails.
- Design: Often feature oversized shell-and-tube heat exchangers with larger fouling factor allowances.
- Materials: May use stainless steel tubes or titanium tubes (for seawater or highly corrosive cooling water).
- Intelligence: Advanced PLCs with touchscreen HMIs, featuring remote monitoring, fault logging, data logging, and energy management.
- Integration: Capable of communicating with primary production line control systems (e.g., SCADA, DCS) for precise regulation.
- Comprehensive: Includes high/low pressure and overcurrent protection, oil pressure differential protection, freeze protection, low-flow protection, phase protection, etc., ensuring safe operation under harsh conditions.
| Parameter / Model | 03WS | 05WS | 06WS | 08WS | 10WD | 12WS | 15WD | 20WD | 25WS | 30WF | 40WF | 50WD | |
| Refrigeration Capacity | kW | 7.7 | 14.2 | 8.98 | 18.95 | 28.4 | 33.5 | 37.9 | 58.2 | 67 | 75.8 | 116.4 | 135.6 |
| ×10⁴kcal/hr | 0.66 | 1.22 | 1.45 | 1.63 | 2.44 | 2.88 | 3.26 | 5 | 5.76 | 6.52 | 10.01 | 11.66 | |
| Consumed Power (kW) | 2.49 | 3.81 | 4.29 | 5.29 | 7.62 | 8.78 | 10.98 | 15.34 | 17.95 | 21.96 | 30.28 | 35.50 | |
| Running Amp (A) | 4.73 | 7.79 | 7.76 | 10.9 | 15.58 | 17.1 | 22.6 | 32.38 | 33.26 | 45.2 | 64.06 | 65.82 | |
| Compressor | Number | 1 | 1 | 1 | 1 | 2 | 1 | 2 | 2 | 1 | 4 | 4 | 2 |
| Power (kW) | 1.94 | 3.26 | 3.74 | 4.74 | 6.52 | 7.68 | 9.48 | 13.14 | 15.75 | 18.96 | 26.28 | 31.5 | |
| Current (A) | 3.63 | 6.69 | 6.66 | 9.80 | 13.38 | 14.90 | 19.6 | 27.98 | 28.86 | 39.2 | 55.96 | 57.72 | |
| Refrigerant | Type | R22 | R410A | R22 | R410A | ||||||||
| Control Mode | External Balance Type Thermal Expansion Valve | ||||||||||||
| Pump | Type | High-Efficiency Low-Noise Centrifugal Pump | |||||||||||
| Power (kW) | 0.55 | 0.55 | 0.55 | 0.55 | 1.1 | 1.1 | 1.5 | 2.2 | 2.2 | 3 | 4 | 4 | |
| Current (A) | 1.1 | 1.1 | 1.1 | 1.1 | 2.2 | 2.2 | 3 | 4.4 | 4.4 | 6 | 8.1 | 8.1 | |
| Head (m) | 22 | 21 | 21 | 20.5 | 25.5 | 24.5 | 23.5 | 27.5 | 27 | 33 | 29 | 29 | |
| Condenser | Water Pipe | DN25 | DN40 | DN50 | DN65 | ||||||||
| Water Flow Rate (m³/h) | 1.73 | 3.11 | 3.70 | 4.25 | 6.22 | 7.32 | 8.51 | 12.74 | 14.99 | 17.01 | 25.47 | 29.99 | |
| Evaporator | Water Pipe | DN25 | DN40 | DN50 | DN65 | ||||||||
| Water Flow Rate (m³/h) | 1.40 | 2.55 | 3.06 | 3.44 | 5.10 | 5.99 | 6.87 | 10.47 | 12.28 | 13.75 | 20.95 | 24.56 | |
| Size | Length (mm) | 900 | 900 | 900 | 1300 | 1300 | 1450 | 1450 | 1800 | 1800 | 2200 | 2500 | 2500 |
| Width (mm) | 650 | 650 | 650 | 800 | 800 | 900 | 900 | 1000 | 1000 | 1350 | 1350 | 1350 | |
| Height (mm) | 1090 | 1090 | 1090 | 1750 | 1750 | 1750 | 1750 | 1800 | 1800 | 1400 | 1800 | 1800 | |
| Tank Volume (L) | 50 | 75 | 90 | 120 | 120 | 160 | 160 | 250 | 300 | 300 | 500 | 500 | |
| Total Weight (kg) | 150 | 220 | 260 | 310 | 360 | 450 | 650 | 850 | 1050 | 1250 | 1350 | 1400 | |