Leave Your Message

Air Cooled Water Chiller

Water chiller integrates a refrigeration system, water tank, and water pump into a compact unit, making it easy to install and highly efficient in cooling. It cools the criculating water to the set low temperature through the refrigeration system. Providing a stable source of low -temperature water for industrial equipment.

    Product Feature

    • Adopt compressor imported from Europe and America;
    • The copper pipe adopts oxygen free welding method;
    • RS485 communication function to realize automatic management(optional);
    vImported advanced components with long service life;
    • Siemens SCHNEIDER.LG.MOELLER. Westis adopted for electrical appliances;
    • Control mode: imported microcomputer or PLC control (optional);
    • Perfect safety protection, fault display, repair and maintenance with out professional personnel;
    • High efficiency evaporator and condenser can save energy by more than 30%.

    Working Principle and System Components

    1. Refrigeration Cycle (consistent with all compression refrigeration systems):
    • Refrigerant absorbs heat from the chilled water in the evaporator, vaporizing into a gas.
    • The low-temperature, low-pressure refrigerant vapor is compressed into a high-temperature, high-pressure gas by the compressor.
    • The high-temperature, high-pressure gas enters the air-cooled condenser, where it releases heat and condenses into a high-pressure liquid through forced convection from fan-driven ambient air.
    • The high-pressure liquid passes through the expansion valve, throttling into a low-temperature, low-pressure wet vapor, which re-enters the evaporator, completing the cycle.
    2.  Core Difference — The Air-Cooled Condenser:
    • This is the fundamental distinction between air-cooled and water-cooled chillers. It consists of copper tube-aluminum fin coil arrays and one or multiple high-power axial fans.
    • The fans force air across the finned coils, transferring heat from the high-temperature refrigerant inside the tubes to the atmosphere.
    3. System Composition (Highly Integrated):
    • Main Unit: The compressor, air-cooled condenser, evaporator, expansion valve, and control system are all integrated within a single steel frame.
    • Auxiliary Components:
    • Chilled Water Circulation Pump: Typically built into the water tank or provided as an external pump set.
    • Insulated Water Tank:Stores chilled water and acts as a buffer for system water volume and temperature stability.
    • Electrical Control Cabinet: Integrates control, protection, and display functions.

    Typical Industrial Applications

    • Plastics Industry: Cooling for injection molding machine molds, directly impacting product quality and cycle time.
    • Chemical & Pharmaceutical: Cooling exothermic reactions in process vessels, controlling reaction rates and safety.
    • Machining & Lasers: Cooling for CNC machine spindles, laser sources, and welding equipment, ensuring precision and longevity.
    • Food & Beverage: Cooling for mixing, fermentation, and packaging processes in production lines.
    • Electronics Industry: Cooling for semiconductor manufacturing, ultrasonic cleaning, and testing equipment.
    • Energy & Metallurgy: Transformer oil cooling, blast furnace auxiliary system cooling.
    16
    15
    14

    Schematic Diagram

    Schematic Diagram

    specification

    Parameter UNIT MODEL
    SC-03AS SC-05AS SC-08AS SC-10AD SC-15AD SC-20AD SC-25AD SC-30AD SC-40AD SC-50AD SC-60AD
    Cooling Capacity Kcal/h 7216 11990 18748 24089 37965 50808.8 61683 74992 97678 116521 156249
    KW 8.39 13.95 21.8 28.01 44.15 59.08 71.72 87.2 113.58 135.49 181.68
    Power Input KW 3.6 5.5 8.6 11 17 22.8 27.7 33.7 42.8 51.1 68.8
    Running Current A 8.8 13.4 20.9 26.7 41.3 55.4 63.1 76.8 97.5 116.5 143.1
    Refrigerant / R22
    Power Supply Type / 3PH-380V-50HZ
    Safety Protection Device / Overload、Inverse Phase、High/Low Pressure、Low Level、Antifreeze Protection, etc
    Compressor Power KW 2.25 3.75 3*2 3.75*2 7.5+3.75 7.5*2 9.4*2 7.5*3 7.5*4 9*4 7.5*6
    Current A 4.8 9.2 15.2 17.2 41.3 36 50 54 66 80 99
    Pump Flow m3/h 4 4 8 8 12 16 20 36 36 36 36
    Phead m 22 22 27 27 31 33 21 20 20 20 20
    Power KW 0.55 0.55 1.1 1.3 1.85 2.6 2.2 4 4 4 4
    Condenser Type / MCHE Or Finned Tubes
    Air Flow m3/h 3000 5000 8000 10000 15000 20000 25000 30000 40000 50000 60000
    Fan Power KW 0.24 0.4 0.64 0.8 1.2 1.6 2 2.4 3.2 3.8 4
    Evaporator Type / Submerged Coil Type Dny Shell And Tube Type
    In/Out Pipe SizeInch Inch DN25 DN25 DN40 DN50 DN50 DN50 DN65 DN65 DN80 DN80 DN80
    Tank Volume L 45 50 110 110 200 260 310 220 255 280 350
    Size length mm 960 1050 1480 1480 1880 2000 2000 2400 2100 2450 3400
    width mm 560 610 720 720 800 900 1000 1100 1600 1750 1800
    height mm 1250 1300 1550 1550 1700 1800 1950 1950 1850 2050 2100

    Products Detail

    air cooled water chiller
    industrial water chiller
    Water chiller

    Leave Your Message